flex 400

I/O extension module flex 400

I/O module for extending the functions of controllers from the REGULA series with flexibility
The flex 400 is designed to extend the functions of controllers from the grandis family by adding additional inputs and outputs. This enables the implementation of an additional heating circuit, for example, or a fresh water station, additional multi-function controllers and an additional energy yield measurement function (depending on the controller software).
Article Description
1340FLEX400-2A-G I/O extension module flex 400

Category:
General Details

Characteristics

  • Minimum installation work
  • Bus line connection to the controller, making direct installation at the heating station possible
  • Prozeda bus interface: ProBusX
  • DIP switch addressing
  • Automatic initialisation
  • Spring-loaded terminals
  • Compact design
  • High protection class IP 54
  • Customer-specific prewiring available
  • Customer-specific prewiring available
  • 1 input for flow sensor (impeller flow sensor or in the form of an interface for a vortex flow sensor)
  • 4 temperature inputs for PT1000 sensor
  • 3 outputs 230V AC
    1 control output for HE pump PWM or 0-10V analog
    1 potential-free output

Possibilities for extension of the REGULA family:

  • grandis 600 SR:
    Connection of up to 2 flex 400 modules
    Control of 2 additional heating circuits
    (1 heating circuit per flex 400))
    Independent yield measurements (1 per flex 400)
  • grandis 650 HK:
    Connection of up to 4 flex 400 modules
    Control of 4 additional heating circuits
    (1 heating circuit per pro flex 400)
    Independent yield measurements (1 per flex 400) If not assigned as a heating circuit, up to 3 additional multifunction controllers *

 

 

Technical Data
Operating voltage:AC 230 Volt, 50 Hz, –10 to +15 %Inputs:Temperature inputs with fine-level surge protection for PT 1000 temperature sensors, measuring range: –30 °C to +250°C
Power consumption:< 2 WProtection:Fuse TR 5 Typ 372, 2 A/T (2 Ampere/slow)
Outputs:Electronic semiconductor relay, 230 V AC, 50 Hz,
min. 10 mA, max. 150 W, with cos φ >=0,9
Ambient temperature:0 to +40 °C
Interface:RS 485 for ProBus / ProBusXStorage temperature:–10 to +60 °C
Control outputs for HE pumps:PWM signal: 1kHz, ViL < 0,5 V DC, ViH > 9 V DC, 10 mA max.
Analog signal: 0 …+10 V DC +/– 3%, 10 mA max.
Housing material:100 % recyclable ABS housing
Total output of all outputs:max. 300 WDimensions:L x W x D in mm 150 × 112 × 70
Protection class:IP30 according to DIN 40050, EN 60529