- Home
- Pump groups
- Heating
- HydroFlex HKU 200
HydroFlex HKU 200
Pump group with integrated control system
Pre-wired system module with integrated control system compatible with REGULA grandis 650 HK via bus cable Two line pump module, pipe clearance 125 mm, equipped with Class A high-efficiency pump with PWM actuation. Optionally with Halm or Grundfos pump. Supply line and return line ball cock with thermometer handle 0 – 160°C. The supply line ball cock is equipped with an adjustable gravity brake. The electronic components of the pump is situated outside the insulation and is air-cooled. The supply line and return line are equipped in addition with a shut-off valve for boiler connections. The pump can be replaced without the system needing to be emptied.Article | Description |
---|---|
1402HS-HKU01-1B-G | HydroFlex HKU200 DN20 |
Categories: Heating, Pump groups
- General Details
- Technical Data
- Video
- Downloads
General Details
Pump group
- HE pump, Class A, delivery height 4 m
- Fully insulated (ENEV)
- Compact design
- System connections with ¾“ female thread (optionally 1“)
- Wall bracket with wall mounting material
- 2 thermometers for indicating supply and return line temperature
- Pipe clearance 125 mm 0 – 160°C
- Supply line and return line ball cock with thermometer handle
- Supply line and return line ball cock for the boiler side
- Supply line ball cock with adjustable gravity brake
- The pump can be replaced without the system needing to be emptied
- Integrated display for indicating values
- Plug-in bus connection
- No other materials required
- 4 stations can be added
Integrated control system
- Compatible with REGULA grandis 650 HK via bus connection
- Manual test mode – Pump on/off
- Display for indicating values, e.g. supply line and return line temperature
- Mains cable with earthing pin plug
- Assignment of the heating circuit
- In and outgoing bus connection with XLR plug and socket
Technical Data
Technical data of pump group
Nominal width: | DN20 | Max. operating pressure: | 10 bar |
Clearance between supply line and return line: | 125 mm | Boiler output configuration: | up to 32KW (for Delta T 20°C) |
Connection: | 3/4" on boiler and heating line side | Delivery height: | depending on the pump installed |
Pump connection: | for pumps with 1" male thread, length 130 mm | KvS value: | 3,3 |
Temperature measuring range of analog indicators: | 0 - 160°C | Dimensions incl. insulation: | H x W x D in mm 490 x 245 x 115 |
Max. operating temperature: | 110°C | ||
Technical data of control system
Operating voltage: | AC 230 Volt, 50 Hz, -10 to +15% | Protection class of terminal: | IP30 according to DIN 40050, EN 60529 |
Mains cable: | Earthing pin plug, with 2m mains cable | Protection class of IO unit: | IP44 according to DIN 40050, EN 60529 |
Standby losses: | 1 W | Ambient temperature: | 0 to +40°C |
Display: | LCD | Storage temperature: | -10 to +60°C |
Bus connection: | each with 1 XLR plug and socket | Housing material: | 100% recyclable ABS housing |
Dimensions of terminal: | H x W x D in mm 144 x 102 x 11 |
Video